After receiving the emergency booking, we attended the property in the NG5 area within 45 minutes.
When an RCD keeps tripping, the switch itself is rarely the problem. It is usually responding to a fault somewhere on the installation. Our first task was therefore to find out which circuit was causing the trip. Systematic fault-finding checks isolated the problem to the downstairs lighting circuits.
Further investigation showed that the issue was a neutral-to-earth (N-E) fault. This type of fault occurs when the neutral conductor comes into contact with earth. It can be difficult to locate, because the circuit may appear to work normally until the RCD detects the imbalance and trips.
We traced the fault along the cable route and found the cause concealed behind shelving. A nail used to fix the shelving roughly 25 years earlier had penetrated the cable. The damage had stayed hidden for decades before it eventually developed into the fault the customer was now experiencing.
We replaced the damaged section of cable, which rectified the fault. After the necessary checks, the affected lighting circuit was returned to service and the electrical supply was restored.
The job shows why it pays to find the real cause of RCD tripping instead of repeatedly resetting the switch. Old, hidden cable damage from fixings such as nails and screws can go unnoticed for years. Careful fault-finding is often the only reliable way to locate it.