We were called out to carry out an emergency EICR at the property in The Park, Nottingham, so the DNO could consider reconnecting the supply.
An EICR combines a visual inspection with testing to check the condition of an electrical installation. Some of those tests are carried out with the power off, known as dead testing. Others, such as earth fault loop impedance and RCD tests, need the supply to be live.
With the supply isolated by the DNO, we carried out a dead-test EICR. Dead tests check things such as the continuity of the protective conductors, the insulation resistance of the cables and correct polarity. Together, they show whether the cables and circuits are in a safe condition to have power restored.
The dead-test EICR confirmed the cables were safe, which gave the DNO the evidence it needed before re-energising the property.
The job isn’t finished with the dead tests. Once the DNO has reconnected the supply, we will return to carry out the full live testing and complete the EICR. That second visit confirms the installation performs correctly under power, including how quickly protective devices disconnect in the event of a fault.
Splitting the EICR into a dead-test stage and a live-test stage meant the owner didn’t have to wait longer than necessary for the power to come back on.